The Brava uses a standard North American 3-prong plug. The wiring within the household needs to be consistent with National Electrical Code for kitchens that use 15-20 AMP circuit breakers. The Brava needs to be connected to an outlet that is supported by a 20 Amp breaker.
The Brava is currently tested and designed for use in the United States and Canada. It is only intended to be connected to a 110V-120V 60Hz circuit. The Brava pulls approximately 1800 Watts.
Important Requirements:
- Connect to a properly grounded three-prong ground-fault current interruption (GFCI) outlet
- Do not connect to a two-pronged outlet using an adaptor
- Do not connect with power converters